Data record tests.relay-59-overvoltage-test.ieee1547-1.type-test
Verified 2026-10-24 Confidence: Medium
The overvoltage trip type test in clause 5.4.2 of IEEE 1547.1-2020 applies the Annex A.3 step function to voltage: the function is set to the end of its adjustable range closest to nominal with the trip time at its minimum, the source is held just short of the set point on its non-trip side and then stepped past it, the voltage at trip is recorded, and the sequence is repeated per phase, at the opposite end of the range, at the maximum trip time and for each overvoltage trip region. Clause 5.4.2.4 passes the test when the unit trips inside the applicable clearing time of IEEE 1547-2018 and its evaluated adjustment ranges cover the allowable ranges.
| Step | Item | Detail |
|---|---|---|
| Source | IEEE 1547.1-2020 | Licensed standard, clause 5.4.2, 5.4.2.4 |
| Data record | tests.relay-59-overvoltage-test.ieee1547-1.type-test | Verified 2026-10-24 |
| Entry | Relay 59 Overvoltage Test | No revisions |
- Subject
- Relay 59 Overvoltage Test (Test methods)
- Kind
- Method fact
- Source
- IEEE 1547.1-2020, clause 5.4.2, 5.4.2.4, Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources, IEEE.
History
| Date | Change |
|---|---|
| 2026-10-24 | created |
| 2026-10-24 | revised |
| 2026-10-24 | review_status unreviewed -> software_reviewed |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record tests.relay-59-overvoltage-test.ieee1547-1.type-test." Protective Relay Reference. 2026-10-24. https://www.protectiverelayreference.com/data/tests.relay-59-overvoltage-test.ieee1547-1.type-test/.
Protective Relay Reference, Data record tests.relay-59-overvoltage-test.ieee1547-1.type-test (Oct. 24, 2026), https://www.protectiverelayreference.com/data/tests.relay-59-overvoltage-test.ieee1547-1.type-test/.
@misc{etr-data-tests-relay-59-overvoltage-test-ieee1547-1-type-test,
title = {Data record tests.relay-59-overvoltage-test.ieee1547-1.type-test},
howpublished = {\url{https://www.protectiverelayreference.com/data/tests.relay-59-overvoltage-test.ieee1547-1.type-test/}},
organization = {Protective Relay Reference},
publisher = {Protective Relay Reference},
year = {2026},
note = {last substantive change 2026-10-24}
}{{cite web |title=Data record tests.relay-59-overvoltage-test.ieee1547-1.type-test |website=Protective Relay Reference |publisher=Protective Relay Reference |url=https://www.protectiverelayreference.com/data/tests.relay-59-overvoltage-test.ieee1547-1.type-test/ |date=2026-10-24 |access-date=}}