Test methods

Test methods applied to electrical power equipment at acceptance and in maintenance, each with its purpose, principle and the standards that govern it.

Test methods per groupProtection: 28; Control: 2; Inspection: 1; Insulation: 1; Ratio: 1; Resistance: 1Protection28Control2Inspection1Insulation1Ratio1Resistance1
Test methods per group. Entries in this family grouped by the equipment or system they apply to. Each bar links to its group below.
Test methods per group: entries per row.
CategoryCount
Protection28
Control2
Inspection1
Insulation1
Ratio1
Resistance1

Control

  1. Control and functional verification

    Control and Functional Verification is specified for electromechanical and solid-state protective relays in acceptance testing at clause 7.9.1.B.4 of ANSI/NETA ATS-2025. Value: electromechanical and solid-state protective relays.

  2. Scada and communication verification

    SCADA and Communication Verification is specified for microprocessor-based protective relays in acceptance testing at clause 7.9.2.B.10 of ANSI/NETA ATS-2025. Value: microprocessor-based protective relays.

Inspection

  1. Visual and mechanical inspection

    Visual and Mechanical Inspection is specified for low-voltage ground-fault protection systems in acceptance testing at clause 7.14.A of ANSI/NETA ATS-2025. Value: low-voltage ground-fault protection systems.

Insulation

  1. Insulation resistance

    Insulation Resistance is specified for low-voltage ground-fault protection systems in acceptance testing at clause 7.14.B.2 of ANSI/NETA ATS-2025. Value: low-voltage ground-fault protection systems.

Protection

  1. Ground fault protection performance

    Ground Fault Protection Performance is specified for low-voltage ground-fault protection systems in acceptance testing at clause 7.14.B.4 of ANSI/NETA ATS-2025. Value: low-voltage ground-fault protection systems.

  2. Protective Relay Element Tests

    Protective Relay Element Tests is addressed in ANSI/NETA ATS-2025.

  3. Relay 21 Distance Test

    Relay 21 Distance Test is addressed in ANSI/NETA ATS-2025.

  4. Relay 25 Sync Check Test

    Relay 25 Sync Check Test is addressed in ANSI/NETA ATS-2025.

  5. Relay 27 Undervoltage Test

    Relay 27 Undervoltage Test is addressed in ANSI/NETA ATS-2025.

  6. Relay 32 Directional Power Test

    Relay 32 Directional Power Test is addressed in ANSI/NETA ATS-2025.

  7. Relay 40 Loss of Field Test

    Relay 40 Loss of Field Test is addressed in ANSI/NETA ATS-2025.

  8. Relay 46 Current Balance Test

    Relay 46 Current Balance Test is addressed in ANSI/NETA ATS-2025.

  9. Relay 46n Negative Sequence Test

    Relay 46n Negative Sequence Test is addressed in ANSI/NETA ATS-2025.

  10. Relay 47 Phase Sequence Test

    Relay 47 Phase Sequence Test is addressed in ANSI/NETA ATS-2025.

  11. Relay 49r Thermal Replica Test

    Relay 49r Thermal Replica Test is addressed in ANSI/NETA ATS-2025.

  12. Relay 49t Temperature Test

    Relay 49t Temperature Test is addressed in ANSI/NETA ATS-2025.

  13. Relay 50 Instantaneous Overcurrent Test

    Relay 50 Instantaneous Overcurrent Test is addressed in ANSI/NETA ATS-2025.

  14. Relay 50bf Breaker Failure Test

    Relay 50bf Breaker Failure Test is addressed in ANSI/NETA ATS-2025.

  15. Relay 51 Time Overcurrent Test

    Relay 51 Time Overcurrent Test is addressed in ANSI/NETA ATS-2025.

  16. Relay 55 Power Factor Test

    Relay 55 Power Factor Test is addressed in ANSI/NETA ATS-2025.

  17. Relay 59 Overvoltage Test

    Relay 59 Overvoltage Test is addressed in ANSI/NETA ATS-2025.

  18. Relay 60 Voltage Balance Test

    Relay 60 Voltage Balance Test is addressed in ANSI/NETA ATS-2025.

  19. Relay 63 Sudden Pressure Test

    Relay 63 Sudden Pressure Test is addressed in ANSI/NETA ATS-2025.

  20. Relay 64 Ground Detector Test

    Relay 64 Ground Detector Test is addressed in ANSI/NETA ATS-2025.

  21. Relay 67 Directional Overcurrent Test

    Relay 67 Directional Overcurrent Test is addressed in ANSI/NETA ATS-2025.

  22. Relay 79 Reclosing Test

    Relay 79 Reclosing Test is addressed in ANSI/NETA ATS-2025.

  23. Relay 81 Frequency Test

    Relay 81 Frequency Test is addressed in ANSI/NETA ATS-2025.

  24. Relay 85 Pilot Wire Monitor Test

    Relay 85 Pilot Wire Monitor Test is addressed in ANSI/NETA ATS-2025.

  25. Relay 87 Differential Test

    Relay 87 Differential Test is addressed in ANSI/NETA ATS-2025.

  26. Relay Time-Delay Timing Test

    Relay Time-Delay Timing Test is addressed in ANSI/NETA ATS-2025.

  27. Relay Volts per Hertz Test

    Relay Volts per Hertz Test is addressed in ANSI/NETA ATS-2025.

  28. Zone selective interlocking

    Zone Selective Interlocking is specified for low-voltage ground-fault protection systems in acceptance testing at clause 7.14.B.8 of ANSI/NETA ATS-2025. Value: low-voltage ground-fault protection systems.

Ratio

  1. Polarity test

    Polarity Test is specified for low-voltage ground-fault protection systems in acceptance testing at clause 7.14.B.5 of ANSI/NETA ATS-2025. Value: low-voltage ground-fault protection systems.

Resistance

  1. Bolted connection resistance

    Bolted Connection Resistance is specified for low-voltage ground-fault protection systems in acceptance testing at clause 7.14.B.1 of ANSI/NETA ATS-2025. Value: low-voltage ground-fault protection systems.