Relay 51 Time Overcurrent Test
Updated 2026-10-24
| Relationship | Entry |
|---|---|
| Governing standard | IEEE C37.112-2018 (IEEE Standard for Inverse-Time Characteristics Equations for Overcurrent Relays) |
Data records
- Relay 51 Time Overcurrent Test is specified for electromechanical and solid-state protective relays in acceptance testing at clause 7.9.1.B.3.15 of ANSI/NETA ATS-2025. Value: electromechanical and solid-state protective relays.
- Relay 51 Time Overcurrent Test is specified for electromechanical and solid-state protective relays in maintenance testing at clause 7.9.1.B.3.15 of ANSI/NETA MTS-2023. Value: electromechanical and solid-state protective relays.
- Relay 51 Time Overcurrent Test is addressed in ANSI/NETA ATS-2025.
- Relay 51 Time Overcurrent Test is addressed in ANSI/NETA MTS-2023.
- A timing check that uses the conformance criteria of IEEE C37.112-2018 places its test points inside the range of multiples of pickup that clause 3.4 names and judges the shape of the curve against the conformance bands, while timing accuracy is judged against the relay manufacturer tolerance because the bands are not accuracy limits.
- For a time-overcurrent element set to one of the standard characteristics of IEEE C37.112-2018, the expected operate time at a test multiple of pickup is computed from the trip equation of clause 3.2 with the relay time dial, which gives the reference against which a measured operate time is compared.
- Tables A.1 and A.2 of IEEE C37.112-2018 record measured constants for two induction relay models that differ from the Table 1 values, which shows that the standard characteristics are mean shapes rather than the exact curve of any particular electromechanical relay.
- When a relay provides the optional reset characteristic of IEEE C37.112-2018, reset timing is checked at multiples of pickup below pickup, over the band that clause 3.4 names, using the reset equation of clause 3.2 with the reset constant scaled by the time dial.
- The test method is named Relay 51 Time Overcurrent Test. Value: Relay 51 Time Overcurrent Test.
Elsewhere in the family
- ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications related entry on Electrical Testing Reference
- ANSI/NETA MTS-2023 Standard for Maintenance Testing Specifications related entry on Electrical Testing Reference
Sources
- ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.9.1.B.3.15. Held as: Purchased single-user copy. Publisher page
- ANSI/NETA MTS-2023, Maintenance Testing Specifications for Electrical Power Equipment and Systems, 2023 edition, NETA. Cited: clause 7.9.1.B.3.15. Held as: Purchased single-user copy. Publisher page
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
- IEEE C37.112-2018, IEEE Standard for Inverse-Time Characteristics Equations for Overcurrent Relays, 2018 edition, IEEE. Cited: clause 3.4; clause 3.2; clause Annex A, Tables A.1 and A.2; clause 3.2, 3.3, 3.4. Held as: Purchased single-user copy.
Obtaining the documents
- ANSI/NETA ATS-2025: publisher catalog or sales page
- ANSI/NETA MTS-2023: publisher catalog or sales page
- IEEE C37.112-2018: publisher catalog or sales page
Changelog (14 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-24 | created (tests.relay-51-time-overcurrent-test.ieeec37-112.conformance-check) | |
| 2026-10-24 | review_status unreviewed -> software_reviewed (tests.relay-51-time-overcurrent-test.ieeec37-112.conformance-check) | |
| 2026-10-24 | created (tests.relay-51-time-overcurrent-test.ieeec37-112.expected-time) | |
| 2026-10-24 | review_status unreviewed -> software_reviewed (tests.relay-51-time-overcurrent-test.ieeec37-112.expected-time) | |
| 2026-10-24 | created (tests.relay-51-time-overcurrent-test.ieeec37-112.induction-relay-curves) | |
| 2026-10-24 | review_status unreviewed -> software_reviewed (tests.relay-51-time-overcurrent-test.ieeec37-112.induction-relay-curves) | |
| 2026-10-24 | created (tests.relay-51-time-overcurrent-test.ieeec37-112.reset-check) | |
| 2026-10-24 | revised (tests.relay-51-time-overcurrent-test.ieeec37-112.reset-check) | |
| 2026-10-24 | review_status unreviewed -> software_reviewed (tests.relay-51-time-overcurrent-test.ieeec37-112.reset-check) | |
| 2026-10-13 | created (tests.relay-51-time-overcurrent-test.equipment.relay.acceptance) | |
| 2026-10-13 | created (tests.relay-51-time-overcurrent-test.equipment.relay.maintenance) | |
| 2026-10-13 | created (tests.relay-51-time-overcurrent-test.governed-by.ansi-neta-ats) | |
| 2026-10-13 | created (tests.relay-51-time-overcurrent-test.governed-by.ansi-neta-mts) | |
| 2026-10-13 | created (tests.relay-51-time-overcurrent-test.title) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Relay 51 Time Overcurrent Test." Protective Relay Reference. 2026-10-24. https://www.protectiverelayreference.com/tests/relay-51-time-overcurrent-test/.
Protective Relay Reference, Relay 51 Time Overcurrent Test (Oct. 24, 2026), https://www.protectiverelayreference.com/tests/relay-51-time-overcurrent-test/.
@misc{etr-tests-relay-51-time-overcurrent-test,
title = {Relay 51 Time Overcurrent Test},
howpublished = {\url{https://www.protectiverelayreference.com/tests/relay-51-time-overcurrent-test/}},
organization = {Protective Relay Reference},
publisher = {Protective Relay Reference},
year = {2026},
note = {last substantive change 2026-10-24}
}{{cite web |title=Relay 51 Time Overcurrent Test |website=Protective Relay Reference |publisher=Protective Relay Reference |url=https://www.protectiverelayreference.com/tests/relay-51-time-overcurrent-test/ |date=2026-10-24 |access-date=}}