Data record tests.relay-27-undervoltage-test.ieee1547-1.type-test
Verified 2026-10-24 Confidence: High
The undervoltage trip type test in clause 5.4.3 of IEEE 1547.1-2020 applies the Annex A.3 step function to voltage: the function is set to the end of its adjustable range closest to nominal with the trip time at its minimum, the source is held just short of the set point on its non-trip side and then stepped past it, the voltage at trip is recorded, and the sequence is repeated for each phase and for all phases together, at the opposite end of the magnitude range, at the maximum trip time and for each undervoltage trip region.
| Step | Item | Detail |
|---|---|---|
| Source | IEEE 1547.1-2020 | Licensed standard, clause 5.4.3 |
| Data record | tests.relay-27-undervoltage-test.ieee1547-1.type-test | Verified 2026-10-24 |
| Entry | Relay 27 Undervoltage Test | No revisions |
- Subject
- Relay 27 Undervoltage Test (Test methods)
- Kind
- Method fact
- Source
- IEEE 1547.1-2020, clause 5.4.3, Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources, IEEE.
History
| Date | Change |
|---|---|
| 2026-10-24 | created |
| 2026-10-24 | revised |
| 2026-10-24 | review_status unreviewed -> software_reviewed |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record tests.relay-27-undervoltage-test.ieee1547-1.type-test." Protective Relay Reference. 2026-10-24. https://www.protectiverelayreference.com/data/tests.relay-27-undervoltage-test.ieee1547-1.type-test/.
Protective Relay Reference, Data record tests.relay-27-undervoltage-test.ieee1547-1.type-test (Oct. 24, 2026), https://www.protectiverelayreference.com/data/tests.relay-27-undervoltage-test.ieee1547-1.type-test/.
@misc{etr-data-tests-relay-27-undervoltage-test-ieee1547-1-type-test,
title = {Data record tests.relay-27-undervoltage-test.ieee1547-1.type-test},
howpublished = {\url{https://www.protectiverelayreference.com/data/tests.relay-27-undervoltage-test.ieee1547-1.type-test/}},
organization = {Protective Relay Reference},
publisher = {Protective Relay Reference},
year = {2026},
note = {last substantive change 2026-10-24}