Data record tests.relay-27-undervoltage-test.ieee1547-1.type-test

Verified 2026-10-24 Confidence: High

The undervoltage trip type test in clause 5.4.3 of IEEE 1547.1-2020 applies the Annex A.3 step function to voltage: the function is set to the end of its adjustable range closest to nominal with the trip time at its minimum, the source is held just short of the set point on its non-trip side and then stepped past it, the voltage at trip is recorded, and the sequence is repeated for each phase and for all phases together, at the opposite end of the magnitude range, at the maximum trip time and for each undervoltage trip region.

ProvenanceIEEE 1547.1-2020 supports data record tests.relay-27-undervoltage-test.ieee1547-1.type-test, which is cited on the entry Relay 27 Undervoltage Test.SOURCEIEEE 1547.1-2020IEEE 1547.1-2020Licensed standard, clause 5.4.3DATA RECORDtests.relay-27-undervoltage-test.ieee1547-1.type-testtests.relay-27-undervolt..Verified 2026-10-24ENTRYRelay 27 Undervoltage TestRelay 27 Undervoltage TestNo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE 1547.1-2020Licensed standard, clause 5.4.3
Data recordtests.relay-27-undervoltage-test.ieee1547-1.type-testVerified 2026-10-24
EntryRelay 27 Undervoltage TestNo revisions
Subject
Relay 27 Undervoltage Test (Test methods)
Kind
Method fact
Source
IEEE 1547.1-2020, clause 5.4.3, Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources, IEEE.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-24created
2026-10-24revised
2026-10-24review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.relay-27-undervoltage-test.ieee1547-1.type-test." Protective Relay Reference. 2026-10-24. https://www.protectiverelayreference.com/data/tests.relay-27-undervoltage-test.ieee1547-1.type-test/.