Data record tests.relay-81-frequency-test.ieee2800.frequency-protection

Verified 2026-10-24 Confidence: High

Clause 9.1 of IEEE 2800-2022 does not require frequency protection on an inverter-based resource plant; where a frequency element is applied it must allow the frequency ride-through of clause 7.3.2 and be coordinated with the transmission system's underfrequency load shedding.

ProvenanceIEEE 2800-2022 supports data record tests.relay-81-frequency-test.ieee2800.frequency-protection, which is cited on the entry Relay 81 Frequency Test.SOURCEIEEE 2800-2022IEEE 2800-2022Licensed standard, clause 9.1DATA RECORDtests.relay-81-frequency-test.ieee2800.frequency-protectiontests.relay-81-frequency..Verified 2026-10-24ENTRYRelay 81 Frequency TestRelay 81 Frequency TestNo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE 2800-2022Licensed standard, clause 9.1
Data recordtests.relay-81-frequency-test.ieee2800.frequency-protectionVerified 2026-10-24
EntryRelay 81 Frequency TestNo revisions
Subject
Relay 81 Frequency Test (Test methods)
Kind
Method fact
Source
IEEE 2800-2022, clause 9.1, Interconnection and Interoperability of Inverter-Based Resources with Transmission Systems, IEEE.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-24created
2026-10-24review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.relay-81-frequency-test.ieee2800.frequency-protection." Protective Relay Reference. 2026-10-24. https://www.protectiverelayreference.com/data/tests.relay-81-frequency-test.ieee2800.frequency-protection/.