Relay 81 Frequency Test
Updated 2026-10-24
Data records
- Relay 81 Frequency Test is specified for electromechanical and solid-state protective relays in acceptance testing at clause 7.9.1.B.3.23 of ANSI/NETA ATS-2025. Value: electromechanical and solid-state protective relays.
- Relay 81 Frequency Test is specified for electromechanical and solid-state protective relays in maintenance testing at clause 7.9.1.B.3.23 of ANSI/NETA MTS-2023. Value: electromechanical and solid-state protective relays.
- Relay 81 Frequency Test is addressed in ANSI/NETA ATS-2025.
- Relay 81 Frequency Test is addressed in ANSI/NETA MTS-2023.
- The overfrequency and underfrequency trip type tests in clauses 5.5.1 and 5.5.2 of IEEE 1547.1-2020 use the rate-limited step of Annex A.4 with frequency as the parameter under test: other control functions are disabled or set so as not to interfere, frequency droop is set to its widest deadband and maximum droop, the magnitude and duration settings start at the minimum of the adjustable range, the source is moved to a starting point and held, then stepped past the set point and held, and the trip frequency and clearing time are recorded, with repeats at the maximum magnitude, at the maximum duration and for each trip region.
- Clause 5.5.1.5 of IEEE 1547.1-2020 requires that the rate of change of frequency during the test transitions stay below the category limit of IEEE 1547-2018 Table 21 or within the unit's demonstrated capability, and that the power level be high enough to separate the trip response from the frequency droop response; the pass criterion has the same form as the voltage trip criterion, and tripping inside the regions where IEEE 1547-2018 Annex H.3 allows either ride-through or trip is accepted.
- For distributed energy resources, clause 6.5.1 and Table 18 of IEEE 1547-2018 set mandatory frequency tripping through two overfrequency functions and two underfrequency functions, with one set of defaults and allowable ranges shared by all three abnormal performance categories; the area electric power system operator specifies the settings after coordinating with the regional reliability coordinator, and the function applies only while the fundamental voltage exceeds a threshold the clause states.
- Clause 9.1 of IEEE 2800-2022 does not require frequency protection on an inverter-based resource plant; where a frequency element is applied it must allow the frequency ride-through of clause 7.3.2 and be coordinated with the transmission system's underfrequency load shedding.
- Clause 9.2 of IEEE 2800-2022 does not require rate-of-change-of-frequency protection; where it is applied it must permit the rate-of-change-of-frequency ride-through of clause 7.3.2.3.5, and clause 7.3.2 with its footnote 111 has frequency computed with filtering under clause 4.4 and cautions against letting a frequency measured during a fault decide a trip.
- The test method is named Relay 81 Frequency Test. Value: Relay 81 Frequency Test.
Elsewhere in the family
- ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications related entry on Electrical Testing Reference
- ANSI/NETA MTS-2023 Standard for Maintenance Testing Specifications related entry on Electrical Testing Reference
- IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces related entry on Interconnection Reference
- IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated Interfaces related entry on Interconnection Reference
- IEEE Standard for Interconnection and Interoperability of Inverter-Based Resources (IBRs) Interconnecting with Associated Transmission Electric Power Systems related entry on Interconnection Reference
Sources
- ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.9.1.B.3.23. Held as: Purchased single-user copy. Publisher page
- ANSI/NETA MTS-2023, Maintenance Testing Specifications for Electrical Power Equipment and Systems, 2023 edition, NETA. Cited: clause 7.9.1.B.3.23. Held as: Purchased single-user copy. Publisher page
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
- IEEE 1547-2018, Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces, 2018 edition, IEEE. Cited: clause 6.5.1, Table 18. Held as: Purchased single-user copy.
- IEEE 1547.1-2020, Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources, 2020 edition, IEEE. Cited: clause 5.5.1, 5.5.2; clause 5.5.1.5, 5.5.2.5. Held as: Purchased single-user copy.
- IEEE 2800-2022, Interconnection and Interoperability of Inverter-Based Resources with Transmission Systems, 2022 edition, IEEE. Cited: clause 9.1; clause 9.2, 7.3.2. Held as: Purchased single-user copy.
Obtaining the documents
- ANSI/NETA ATS-2025: publisher catalog or sales page
- ANSI/NETA MTS-2023: publisher catalog or sales page
- IEEE 1547-2018: publisher catalog or sales page
- IEEE 1547.1-2020: publisher catalog or sales page
- IEEE 2800-2022: publisher catalog or sales page
Changelog (19 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-24 | created (tests.relay-81-frequency-test.ieee1547-1.type-test) | |
| 2026-10-24 | revised (tests.relay-81-frequency-test.ieee1547-1.type-test) | |
| 2026-10-24 | review_status unreviewed -> software_reviewed (tests.relay-81-frequency-test.ieee1547-1.type-test) | |
| 2026-10-24 | created (tests.relay-81-frequency-test.ieee1547-1.type-test-requirements) | |
| 2026-10-24 | revised (tests.relay-81-frequency-test.ieee1547-1.type-test-requirements) | |
| 2026-10-24 | review_status unreviewed -> software_reviewed (tests.relay-81-frequency-test.ieee1547-1.type-test-requirements) | |
| 2026-10-24 | created (tests.relay-81-frequency-test.ieee1547.trip-requirements) | |
| 2026-10-24 | revised (tests.relay-81-frequency-test.ieee1547.trip-requirements) | |
| 2026-10-24 | review_status unreviewed -> software_reviewed (tests.relay-81-frequency-test.ieee1547.trip-requirements) | |
| 2026-10-24 | created (tests.relay-81-frequency-test.ieee2800.frequency-protection) | |
| 2026-10-24 | review_status unreviewed -> software_reviewed (tests.relay-81-frequency-test.ieee2800.frequency-protection) | |
| 2026-10-24 | created (tests.relay-81-frequency-test.ieee2800.rocof-protection) | |
| 2026-10-24 | revised (tests.relay-81-frequency-test.ieee2800.rocof-protection) | |
| 2026-10-24 | review_status unreviewed -> software_reviewed (tests.relay-81-frequency-test.ieee2800.rocof-protection) | |
| 2026-10-13 | created (tests.relay-81-frequency-test.equipment.relay.acceptance) | |
| 2026-10-13 | created (tests.relay-81-frequency-test.equipment.relay.maintenance) | |
| 2026-10-13 | created (tests.relay-81-frequency-test.governed-by.ansi-neta-ats) | |
| 2026-10-13 | created (tests.relay-81-frequency-test.governed-by.ansi-neta-mts) | |
| 2026-10-13 | created (tests.relay-81-frequency-test.title) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Relay 81 Frequency Test." Protective Relay Reference. 2026-10-24. https://www.protectiverelayreference.com/tests/relay-81-frequency-test/.
Protective Relay Reference, Relay 81 Frequency Test (Oct. 24, 2026), https://www.protectiverelayreference.com/tests/relay-81-frequency-test/.
@misc{etr-tests-relay-81-frequency-test,
title = {Relay 81 Frequency Test},
howpublished = {\url{https://www.protectiverelayreference.com/tests/relay-81-frequency-test/}},
organization = {Protective Relay Reference},
publisher = {Protective Relay Reference},
year = {2026},
note = {last substantive change 2026-10-24}
}{{cite web |title=Relay 81 Frequency Test |website=Protective Relay Reference |publisher=Protective Relay Reference |url=https://www.protectiverelayreference.com/tests/relay-81-frequency-test/ |date=2026-10-24 |access-date=}}